Watlow DIN-A-MITE® D SCR Power Controller

up to 100 amps
Watlow DIN-A-MITE® D SCR Power Controller
The DIN-A-MITE® D silicon controlled rectifier (SCR) power controller provides an inexpensive, versatile product for controlling heat in an efficient package. This controller is designed and manufactured with the quality features expected from Watlow®. The mounting footprint matches that of the industry standard mercury displacement relay, but there is no need to worry about mercury, the DIN-A-MITE controller is mercury free.

The DIN-A-MITE Style D is capable of zero cross switching up to 100 amperes single-phase, at 600VAC at 86°F (30°C), depending on the model selected. Combining the input of two or three controllers allows control of three-phase loads. The controller is completely touch-safe and includes on-board, front-accessible, semiconductor fuses. Options
include a current transformer for load current monitoring and a shorted output alarm. The controller is UL® 508, C-UL® and CE approved making it ideal for panels and cabinets that require agency approvals.

Variable time-base, 4-20mA process control and VAC/VDC input contactor options are available. All options are model number dependent and factory configurable. This power controller also includes 200KA short circuit current rating (SCCR) tested up to 480VAC to minimize damage in the event of a short circuit when used with required fusing.


User Manual (EN)
Manuel de l'Utilisateur (FR)
Manual del Usuario (ES)

Watlow: Your Heat Solutions Resource Brochure (EN)
Watlow: Vos Solutions de Chauffage Brochure (FR)
Back to Watlow DIN-A-MITE® SCR Power Controllers

Product Features

200KA SCCR with proper fusing
  • Minimizes damage in the event of a short circuit
Standard panel mount
  • Provides same mount as industry standard 100A MDR
Compact size
  • Reduces panel space and cost
Touch-safe terminals
  • Increases safety for installer and user
Mercury free
  • Assures environmental safety
Faster switching with solid state
  •  Saves energy and extends heater life
UL® 508 listed, C-UL®, RoHS 2 and CE with filter
  • Meets applications requiring agency approval
Back-to-back SCR design
  • Ensures a rugged design
On-board semiconductor fusing
  • Provides quick access with no extra mounting necessary

Product Specifications

Amperage:
  • Max. surge current for 16.6ms, 1,800A peak
  • Latching current: 500mA max.
  • Holding current: 200mA max.
  • Power dissipation is 1.4 watts per ampere switched including on-board fusing
  • 200KA SCCR, Type 1 and 2 approved with the recommended fusing; see user manual
Line Voltage:
  • 24 to 48VAC units: 20VAC min. to 53VAC max.
  • 100 to 240VAC units: 48VAC min. to 265VAC max.
  • 277 to 480VAC units: 85VAC min. to 528VAC max.
  • 277 to 600VAC units: 85VAC min. to 660VAC max.
  • 50/60Hz independent ±5%
Control Mode, Zero Cross:
  • Control option C: VDC input, contactor output
  • Control option K: VAC input, contactor output
  • To increase service life, the cycle time should be less than three seconds
  • Control option F: 4 to 20mA DC input, variable time-base control output
Control Input:
  • AC contactor: 24VAC ±10%, 120VAC +10/-25%, 240VAC +10/-25% @ 25 mA max. per controlled leg
  • DC contactor: 4.5 to 32VDC: max. current @ 4.5VDC is 8mA per leg
  • Loop powered linear current 4 to 20mA DC: loop-powered, control option F0 only (requires current source with 8.0VDC available, no more than two DIN-A-MITE inputs can be connected in series)
Shorted SCR Alarm Option:
Alarm state when the input command signal off and a 15A or more load current is detected by the current transformer
Alarm Output:
  • Energizes on alarm, non-latching
  • Triac 24 to 240VAC external supply with a current rating of 300mA @ 77°F (25°C)
Current Sensing:
On-board current transformer (CT), typically 0.2VAC output signal per ampere sensed into 1,000Ω load
Agency Approvals:
  • CE with proper filter: 204/108/EC Electromagnetic Compatibility Directive EN 61326-1: Industrial Immunity Class A Emissions Not suitable for Class B emissions environment 2006/95/EC Low Voltage Directive EN 50178 Safety Requirements
  • UL® 508-listed and C-UL® File E73741
Control Input Terminals:
Compression: will accept 26 to 12 AWG (0.13 to 3.3 mm2) wire
Line and Load Terminals:
Compression: will accept 6 to 2 AWG (13.3 to 33.6 mm2) wire
Operating Environment:
  • Operating temperature range: -4 to 176°F (-20 to 80°C)
  • 0 to 90% RH (relative humidity), non-condensing
  • Vibration: 2 g, 10Hz to 150Hz, applied in any one of three axes
  • Storage temperature: -40 to 185°F (-40 to 85°C)
  • Insulation tested to 3,000 meters
  • Installation Category III, pollution degree 2
Mounting:
  • Back-panel mounting; fits the same mounting pattern as a 100A, single-phase mercury displacement relay
  • On-board semiconductor fusing
Dimensions:
  • 7.3 in. (185 mm) high x 2.6 in. (66 mm) wide x 9.4 in. (239 mm) deep
  • Weight: 6.5 lb (2.95kg)

Din-a-mite D Code Numbers

Part Number Description
DD10-02C0-0000 Din-a-mite D, 1 phase, 1 controlled leg, 80A @ 50˚C (122˚F), 24 to 48VAC, 4.5 to 32VDC contactor
DD10-02C0-1000 Din-a-mite D, 1 phase, 1 controlled leg, 80A @ 50˚C (122˚F), 24 to 48VAC, 4.5 to 32VDC contactor
DD10-02C0-S000 Din-a-mite D, 1 phase, 1 controlled leg, 80A @ 50˚C (122˚F), 24 to 48VAC, 4.5 to 32VDC contactor
DD10-02F0-0000 Din-a-mite D, 1 phase, 1 controlled leg, 80A @ 50˚C (122˚F), 24 to 48VAC, 4 to 20mA DC proportional
DD10-02F0-1000 Din-a-mite D, 1 phase, 1 controlled leg, 80A @ 50˚C (122˚F), 24 to 48VAC, 4 to 20mA DC proportional
DD10-02F0-S000 Din-a-mite D, 1 phase, 1 controlled leg, 80A @ 50˚C (122˚F), 24 to 48VAC, 4 to 20mA DC proportional
DD10-02K1-0000 Din-a-mite D, 1 phase, 1 controlled leg, 80A @ 50˚C (122˚F), 24 to 48VAC, 22 to 26VAC contactor
DD10-02K1-1000 Din-a-mite D, 1 phase, 1 controlled leg, 80A @ 50˚C (122˚F), 24 to 48VAC, 22 to 26VAC contactor
DD10-02K1-S000 Din-a-mite D, 1 phase, 1 controlled leg, 80A @ 50˚C (122˚F), 24 to 48VAC, 22 to 26VAC contactor
DD10-02K2-0000 Din-a-mite D, 1 phase, 1 controlled leg, 80A @ 50˚C (122˚F), 24 to 48VAC, 100 to 120VAC contactor
DD10-02K2-1000 Din-a-mite D, 1 phase, 1 controlled leg, 80A @ 50˚C (122˚F), 24 to 48VAC, 100 to 120VAC contactor
DD10-02K2-S000 Din-a-mite D, 1 phase, 1 controlled leg, 80A @ 50˚C (122˚F), 24 to 48VAC, 100 to 120VAC contactor
DD10-02K3-0000 Din-a-mite D, 1 phase, 1 controlled leg, 80A @ 50˚C (122˚F), 24 to 48VAC, 200 to 240VAC contactor
DD10-02K3-1000 Din-a-mite D, 1 phase, 1 controlled leg, 80A @ 50˚C (122˚F), 24 to 48VAC, 200 to 240VAC contactor
DD10-02K3-S000 Din-a-mite D, 1 phase, 1 controlled leg, 80A @ 50˚C (122˚F), 24 to 48VAC, 200 to 240VAC contactor
DD10-24C0-0000 Din-a-mite D, 1 phase, 1 controlled leg, 80A @ 50˚C (122˚F), 100 to 240VAC, 4.5 to 32VDC contactor
DD10-24C0-1000 Din-a-mite D, 1 phase, 1 controlled leg, 80A @ 50˚C (122˚F), 100 to 240VAC, 4.5 to 32VDC contactor
DD10-24C0-S000 Din-a-mite D, 1 phase, 1 controlled leg, 80A @ 50˚C (122˚F), 100 to 240VAC, 4.5 to 32VDC contactor
DD10-24F0-0000 Din-a-mite D, 1 phase, 1 controlled leg, 80A @ 50˚C (122˚F), 100 to 240VAC, 4 to 20mA DC proportional
DD10-24F0-1000 Din-a-mite D, 1 phase, 1 controlled leg, 80A @ 50˚C (122˚F), 100 to 240VAC, 4 to 20mA DC proportional
DD10-24F0-S000 Din-a-mite D, 1 phase, 1 controlled leg, 80A @ 50˚C (122˚F), 100 to 240VAC, 4 to 20mA DC proportional
DD10-24K1-0000 Din-a-mite D, 1 phase, 1 controlled leg, 80A @ 50˚C (122˚F), 100 to 240VAC, 22 to 26VAC contactor
DD10-24K1-1000 Din-a-mite D, 1 phase, 1 controlled leg, 80A @ 50˚C (122˚F), 100 to 240VAC, 22 to 26VAC contactor
DD10-24K1-S000 Din-a-mite D, 1 phase, 1 controlled leg, 80A @ 50˚C (122˚F), 100 to 240VAC, 22 to 26VAC contactor
DD10-24K2-0000 Din-a-mite D, 1 phase, 1 controlled leg, 80A @ 50˚C (122˚F), 100 to 240VAC, 100 to 120VAC contactor
DD10-24K2-1000 Din-a-mite D, 1 phase, 1 controlled leg, 80A @ 50˚C (122˚F), 100 to 240VAC, 100 to 120VAC contactor