- Control input and indication light
- Alarm output and indication light
- Current limit indication LED
- See output rating curves on the next page
- Max. surge current for 16.6ms, 1,350A peak
- Max. I2t for fusing is 9100A2s
- Latching current: 500mA max.
- Holding current: 200mA max.
- Fan current: 0.14A for 24VDC; 0.12A for 120VAC; 0.06A for 240VAC
- Off-state leakage 1mA at 77°F (25°C) max.
- Power dissipation: 1 watt per ampere per leg switched
- 200KA SCCR, Type 1 and 2 approved with the recommended fusing; see user manual
- 24 to 48VAC units: 20.4VAC min. to 53VAC max.
- 100 to 240VAC units: 48VAC min. to 265VAC max.
- 277 to 600VAC units: 85VAC min. to 660VAC max.
- 100 to 120VAC, 200 to 208VAC, 230 to 240VAC, 277VAC, 400VAC, 480VAC, 600VAC, +10/-15%, 50 to 60Hz independent ±5% (control options L, P and S)
Alarm state when the input command signal is off and a 10A or more load current is detected by the current transformer (two turns required for 5A and three turns for 2.5A)
Alarm state when the input command signal is on and the load current detected by the current transformer is 20% less than customer adjusted set point
- Energizes on alarm, non-latching
- Triac 24 to 240VAC, external supply with a current rating of 300mA @ 77°F (25°C), 200mA @ 122°F (50°C), 100mA @ 176°F (80°C) and a holding current of 200μA with a latching current of 5mA typical
- CE with proper filter: 204/108/EC electromagnetic compatibility directive EN 61326-1: industrial immunity Class A emissions not suitable for Class B environments Phase angle and phase angle with current limit (control options P and L) are not CE approved for conducted or radiated emissions 2006/95/EC low voltage directive EN 50178 safety requirements installation category III, pollution degree 2
- UL® 50 Type 4X enclosure, Class 1, Div. 2 per ANSI/ISA 12.12.01. Through-wall heat sink models T4 File 184390
- UL® 508 listed and C-UL® File E73741
- 2011/65/EU RoHS 2
- Shock and vibration tested to IEC 60068-2-32
- Vibration tested to IEC 60068-2-6
- Compression: will accept 24 to 16 AWG (0.2 to 1.5 mm2) wire
- Torque to 4.4 in. lb (0.5 Nm) max. with a 1/8 in. (3.5 mm) blade screwdriver
- Compression: will accept 14 to 3 AWG (2.5 to 25 mm2) wire
- Torque to 24 in. lb (2.7 Nm) max. with a 1/4 in. (6.4 mm) blade screwdriver, or a type 1A, #2 Pozi driver
- See the output rating curve chart on next page
- 0 to 90% RH (relative humidity), non-condensing
- Storage temperature: -40 to 185°F (-40 to 85°C)
- Operating temperature: -29 to 176°F (-34 to 80°C)
- Insulation tested to 3,000 meters
DIN EN 50022, 35 mm by 7.5 mm
Four mounting holes No. 6 to No. 8 (M3 to M4) fastener
See page 4 for through-wall panel cutout (Note: Mount cooling fins vertically.)
- Control Mode, Zero-Cross: Control option C: VDC input, contactor output
- Control option K: VAC input, contactor output
- To increase service life on contactor models, the cycle time should be less than three seconds
- Control option F: 4 to 20mA DC input, variable time-base control output
- AC contactor: 24VAC ±10%, 120VAC +10/-25%, 240VAC +10/-25% @ 25mA max. per controlled leg
- DC contactor: 4.5 to 32VDC: max. current @ 4.5VDC is 6mA per leg, add 2mA per LED used to the total current
- Loop powered linear current 4 to 20mA DC: loop-powered, control option F0 only (requires current source with 8.0VDC available, no more than two DIN-A-MITE inputs can be connected in series)
- Operation: With control option S (single-cycle, variable time-base) the output is not on for more than one consecutive AC cycle below 50% power and not off for more than one consecutive AC cycle above 50% power
- Phase angle control, single-phase only
- 0 to 20mA, 4 to 20mA, 0 to 5VDC, 1 to 5VDC and 0 to 10VDC
- Input impedance 250Ω for 4mA to 20mA, 5kΩ for linear voltage input
100 to 120VAC, 200 to 208VAC, 230 to 240VAC, 277VAC, 400VAC, 480VAC and 600VAC, ±10%
±5% input to output power over 0 to 100% of span between calibration points
±5% input to output power, as referenced to a sinusoidal power curve, between calibration points
Better than 0.1% of input span with respect to output change
- Typically: 5 second soft start on power up
- Soft start on thermostat over temperature
- Soft start on 1/2 cycle drop out detection
- 1 second soft start on set point change
- Manual control kit (1kΩ potentiometer) 08-5362
- Alarm option is not available on control options P or L