Product Specifications
Power Bases
• Single-phase, 1 controlled leg (2 SCRs)
• Three-phase, 2 controlled legs (4 SCRs)
• Three-phase, 3 controlled legs (6 SCRs)
Load Amp Range
• 35A to 700A @ 40°C ambient
• Amperage derating curve for other ambient temperatures
SCR and Amperage Rating
• Latching current 1A min.
• Power dissipation: approximate 1.25 to 1.5 watts per amp per controlled leg
• Leakage current: 15mA
• SCCR rating 100,000A up to 600VAC
Line and Load Voltage Range
• 24 to 480V
• 24 to 600V
• 24 to 690V
Voltages -/+ 10% min./max.
690VAC only available for 60A and greater models
• Isolation voltage 2500V
Voltage frequency
• 50 to 60Hz
• Automatically compensates for 47 to 70Hz
Controller Operating Supply Voltage
Line Voltage (VAC) RMS
• 100/120VAC (90 to 135VAC Max. Operating Range)
• 200/208/220/230/240VAC (180 to 265VAC Max. Operating Range)
• 277VAC (249 to 305VAC Max. Operating Range)
• 380/400/415/440/480VAC (342 to 528VAC Max. Operating Range)
• 600VAC (540 to 660VAC Max. Operating Range)
• 690VAC (621 to 759VAC Max. Operating Range)
Control Modes and Load Types
• Voltage, voltage squared, current, current squared, power, open loop and external • All control modes available with any firing type combination • Normal resistive loads: nichrome, infrared lamps; medium and long waveform • Others: Moly (Kanthal® Super), transformers, silicon carbide, UV lamps, tungsten
Digital Inputs 1 and 2
• ON >=4VDC, OFF <= 1VDC
• 4-30VDC @ 5mA max.
• Digital input functions: enable, change to V feedback, local/remote set point enable, change firing between phase angle and default firing mode, ref 1 / 2 selection, log enable, bakeout enable
• A switched VDC control output can be connected to the digital input as an open loop control mode command signal
Output Control Firing Types
• Zero crossing
• Single cycle
• Burst firing with delayed triggering, safety ramp and peak current limit options
• Burst firing with soft start option (phase angle soft start switching over to burst firing)
• Phase angle with soft start option
• 1-phase models will include phase angle firing
• 2-phase models are not available with phase angle firing
• 3-phase models from 60 to 500 amps will include phase angle firing
• 3-phase models from 35 to 40 amp are not available with phase angle firing
• All models capable of phase angle firing can include Current Limiting and Heater Bake out functions • Heater Bakeout and current limit functions require the Current Limit Loop option
• Current Limit Loop can be ordered as an option in digit 10 of the part number
• If a model does not have phase angle firing it cannot do Current Limiting, Heater Bakeout, Start Ramp, Safety Ramp or Delayed Triggering
• Half cycle with start ramp and peak current limit options
Analog Inputs 1 and 2
Voltage
• 0-10VDC
• 15KΩ impedance
Current
• 4-20mA, 0-20mADC
• 100Ω impedance
Potentiometer
• 10KΩ min.
Analog Output 1
• 0 to 20mA or 4 to 20mA into 500Ω max. load with 50μA nominal resolution
• 0 to 10VDC into a 500Ω min. load with 50mV nominal resolution
Analog Output Functions
• Retransmit: Load voltage, current, power or measured input (Note: If using both Analog Retransmit (digit 10, options A or D) and Additional Wired Communication (digit 12, options 1-5) an external power supply will be required. Watlow power supply part number: 0847-0299-0000
Descriptions: AC/DC power supply converter for 90-263VAC to 24VDC, 1.30A, 31W.)
Electromechanical Relay Output
• Form C, 30VDC max. at 1A resistive load or 0.5A at 125VAC, 6000 cycles at 30VDC, 100,000 cycles at 120VAC
Relay Functions
• Alarm output options for heater open break, SCR short or current limit, heat sink/ambient over-temperature
DC Power Supply for Digital Inputs and Potentiometer remote set point input
• 10VDC @ 10mA max.
Fusing
• Integrated semiconductor fuse
• Refer to amperage chart for I2T fuse values
Diagnostics Annunciation Messages
• Heater break (open), SCR short circuit (closed), current limit, thermal switch, SD card error, comms watchdog error, bakeout in process, aux. voltage too low or high, voltage line loss
Operator Interface
• 0.96 in. white OLED display with 128 x 64 pixel resolution
• L/R, F UP and DOWN arrow keys
• 4 discrete LED indicators for local/remote mode, enable, communications and alarm
Connectivity
• EIA 485, Modbus® RTU
• Modbus® TCP Ethernet
• EtherNet/IP™
• Wi-Fi
• USB 2.0 device connection
• PROFIBUS DP
• PROFINET
(Note: If using both Analog Retransmit (digit 10, options A or D) and Additional Wired Communication (digit 12, options 1-5) an external power supply will be required. Watlow power supply part number: 0847-0299-0000 Descriptions: AC/DC power supply converter for 90-263VAC to 24VDC, 1.30A, 31W.)
Configuration
• PC software tool and RS485, USB port, or on-board keypad and LED display
Integrated Data Logging
• Storage: 16 GB SD memory card
• .CSV file type
• User programmable logging intervals 1 to 255 seconds
• Up to 10 parameters selectable by user: line frequency, output voltage (RMS), output current (RMS), output power (average), status, commands, set point, current limit set point (RMS), load resistance, input voltage (RMS)
Real Time Clock and Battery Back-up
• Typical battery life: 5 years at 77°F (25°C)
• CR2032 field replaceable battery
Cooling mode
• Forced air (fan)
• 24VDC, 120 or 240VAC, 17 watts per fan used Control Terminals
• Terminals are touch safe, removable, 12 to 22 AWG
Line and Load Terminals
• Compatible with crimp lug terminals or busbar
• Refer to user manual for wire size, compression and torque requirements
Mounting
• Panel mounting with screws
• Must be mounted with heat sink fins in vertical orientation
Environment
• 0 to 40°C without derating
• 5 to 90% RH (relative humidity), non-condensing
• Up to 2000 meters above sea level max.
• Over 1000 meters of altitude reduce the nominal current by 2% for each 100 meters
• Storage temperature -25 to 70°C max.
Agency Approval and Regulatory
• cULus 508 Listed File E73741
• cUL® Listed to C22.2 No. 14
• CE EMC Directive 2014-30-EU, EN 60947-4-3 Class A Emissions
• CE Safety Directive 2014-35-EU, EN 60947-4-1, -4-3
• IP20 with all covers in place
• RoHS 2011-65-EU
• W.E.E.E 2012-19-EU
• 690VAC units not covered by UL®
Accessories
• Free Watlow ASPYRE configuration software on the Watlow website at http://www.watlow.com/en/resources-and-support/Technical-Library/Software-and-Demos
• 6 ft USB 2.0 to micro USB device cable 0219-0480-0000
• Fuses - see datasheet